An industrial gas site had a start/stop panel that was not rated for a hazardous area. They needed a like-for-like replacement, with the same controls in the same layout, but fully ATEX compliant for installation in Zone 1.
What we built
A 700 x 700 x 250mm enclosure in 2mm pre-galvanised mild steel, powder coated RAL 7035 light grey. The left-hand hinged lift-off door hangs on 316L stainless body hinges and is secured by chrome-plated die-cast zinc camlocks for quick access.
The door carries the full set of 29 pushbuttons and 28 indicator modules in neat rows, matching the existing panel. Inside, a galvanised mounting plate on four M6 x 25mm rear studs carries WDU 2.5mm² terminals tagged to specification, kept tidy in two runs of 60 x 80mm grey slotted trunking. There is an M10 internal/external earth stud on the left-hand side, four bolt-on wall lugs, and our standard one-piece 6mm silicone gasket for the IP66 seal.
The customer chose to fit their own legend labels.
Why Ex db eb
Pushbuttons and indicators contain contacts that spark. In an Ex db eb panel those parts sit inside small flameproof (Ex db) operator units, while the enclosure and terminals use increased safety (Ex eb). This avoids the weight and cost of a fully flameproof box. Our Ex db eb guide explains the combination.