← Resources

What do IP ratings mean for electrical enclosures?

IP65, IP66, IP67, IP68, what each digit means, what tests are passed, and how to choose the right rating for your installation environment.

Updated

What is an IP rating?

An IP (Ingress Protection) rating is a two-digit code defined by IEC 60529 (EN 60529) that tells you how well an enclosure resists the entry of solid objects and liquids. It replaces vague marketing terms like "waterproof" or "dustproof" with a precise, testable standard.

The code looks like IP66 or IP67. The first digit covers solids; the second covers liquids. A rating of IP66 means dust-tight (first digit 6) and protected against powerful water jets from any direction (second digit 6).

If a digit is replaced by X, for example, IPX7, it means that category was not tested, not that protection is zero.

IP65, IP66, IP67 and IP68 in one line

  • IP65 means dust-tight and protected against low-pressure water jets (6.3 mm nozzle, 12.5 litres per minute) from any direction.
  • IP66 means dust-tight and protected against powerful water jets (12.5 mm nozzle, 100 litres per minute) from any direction, eight times the water of the IP65 test.
  • IP67 means dust-tight and protected against temporary immersion: 30 minutes with the lowest point 1 m under water.
  • IP68 means dust-tight and protected against continuous immersion, at a depth and duration the manufacturer states, which must be more severe than IP67.

Ingress protection ratings are defined by IEC 60529 (EN 60529 in Europe). Both digits are tested separately, which is why IP66 and IP67 are different tests rather than a ladder.

IP65 vs IP66 vs IP67: the test figures

Test (IEC 60529)IP65IP66IP67
Dust (first digit 6)Dust-tightDust-tightDust-tight
Water exposureWater jetsPowerful water jetsTemporary immersion
Nozzle diameter6.3 mm12.5 mmNone (submerged)
Water flow12.5 L/min ±5%100 L/min ±5%None
Approximate pressure30 kPa100 kPaAbout 10 kPa at 1 m depth
Distance or depth2.5–3 m from the nozzle2.5–3 m from the nozzleLowest point 1 m below the surface
Duration1 min per m² of surface, at least 3 min1 min per m² of surface, at least 3 min30 min
Typical useSheltered outdoor, rainExposed outdoor, coastal, offshore, hose-downPits, chambers, flood risk

IP66 and IP67 test different things: jets versus immersion. An enclosure that must survive both should be marked with a dual rating such as IP66/IP67. indEx iTB and iSTB stainless enclosures are rated IP66; iGRP enclosures are rated IP66 and IP67.

Illustration showing IP66 rating, solid and liquid protection digits annotated
Illustration showing IP66: the first digit (6) means dust-tight; the second digit (6) means protection against powerful water jets

How to read the IP code

PositionWhat it coversRange
First digitProtection against solid objects and touch0 – 6
Second digitProtection against water / liquids0 – 9K
X (either position)Not tested / not specified,
IP Rating chart showing solid and liquid protection digits side by side
IP rating structure, first digit (solid protection, 0–6) and second digit (liquid protection, 0–9K)
Optional letters in IP codes, W, S, D, H, M, F suffixes explained
Optional letters that may follow the two digits in an IP code

First digit, solid particle protection (0–6)

DigitProtection levelTypical use
0No protectionExposed components
1Objects ≥ 50 mm (back of hand)Large open equipment
2Objects ≥ 12.5 mm (finger)Standard indoor accessories
3Objects ≥ 2.5 mm (tools, thick wire)Older electrical enclosures
4Objects ≥ 1 mm (fine wire)Control panel enclosures
5Dust-protected (limited ingress, no harmful deposit)Factory control boxes
6Dust-tight (complete, no ingress)ATEX and outdoor enclosures
IP rating first digit 0 to 6, solid particle protection levels
First digit values 0–6: solid particle and contact protection levels

A higher first digit includes all lower levels, an IP6X enclosure also meets IP5X, 4X, and so on. For hazardous area and outdoor electrical enclosures, you will almost always need digit 5 (dust-protected) or 6 (dust-tight).

Second digit, liquid ingress protection (0–9K)

DigitProtectionTest conditionExample uses
0None,Indoor dry locations
1Dripping water (vertical)1 mm/min rainfall, 10 minMinimal condensation
2Dripping water at 15° tilt4 positions, 10 min totalCovered outdoor
3Spraying water up to 60°Oscillating tube, 10 min (or spray nozzle, at least 5 min)Outdoor lighting under eaves
4Splashing water from any direction10 min, any directionOutdoor outlets, garden lighting
5Water jets (6.3 mm nozzle, 12.5 L/min)3 min, any directionOutdoor junction boxes, IP65 cameras
6Powerful jets (12.5 mm nozzle, 100 L/min)3 min, any directionShip deck equipment, IP66 enclosures
7Immersion up to 1 m for 30 minSubmerged at 1 m depthOutdoor connectors, rugged phones
8Continuous immersion (depth specified by manufacturer)Manufacturer-definedSubmersible pumps, underwater lighting
9 / 9KHigh-pressure hot water jets (80 °C, 80–100 bar). IPX9 is in IEC 60529; IPX9K is the equivalent in ISO 20653Close-range, 10–15 cmFood processing, steam cleaning, vehicle wash
IP rating second digit 0 to 9K, liquid ingress protection levels
Second digit values 0–9K: liquid ingress protection levels and test conditions
Water protection levels 1–6 are cumulative. But levels 7 and 8 (immersion) are not automatically implied by level 6 (jets). An IP67 device passed the immersion test; it may not have passed the jet test. Where both are needed, look for a dual rating such as IP66/IP68.

Common IP ratings and what they mean in practice

RatingWhat it meansTypical applications
IP20Finger-safe; no water protectionIndoor electronics, PC power supplies
IP44Objects > 1 mm; splashing water from any directionBathroom lighting, covered outdoor
IP54Dust-protected; splashing waterSheltered outdoor control boxes
IP65Dust-tight; low-pressure jetsOutdoor cameras, junction boxes
IP66Dust-tight; powerful jetsATEX terminal boxes, marine deck equipment
IP67Dust-tight; immersion up to 1 m / 30 minOutdoor connectors, rugged smartphones
IP68Dust-tight; continuous immersion (depth per manufacturer)Submersible pumps, underground junctions
IP69KDust-tight; high-pressure hot water jetsFood/dairy processing, truck wash

For most outdoor electrical enclosures and ATEX installations, IP54 is the minimum spec, but IP66 is the premium specification from indEx Enclosures. IP68 is only necessary for continuous submersion applications.

IP ratings vs NEMA ratings

NEMA (National Electrical Manufacturers Association) ratings are the North American equivalent, but they are not directly interchangeable with IP ratings. NEMA covers additional factors that IP does not, corrosion resistance, icing, and hazardous atmospheres.

NEMA typeApproximate IP equivalentKey difference from IP
NEMA 4IP66NEMA 4 also covers ice formation
NEMA 4XIP66NEMA 4X adds corrosion resistance
NEMA 6IP67NEMA 6 covers ice and brief submersion
NEMA 6PIP68NEMA 6P covers prolonged submersion
NEMA 12IP52Indoor; limited dust and drip only

If a project requires NEMA compliance (common in North America), specify the NEMA type explicitly, don't assume an IP-rated enclosure meets the full NEMA requirement just because the ingress numbers align.

Common misconceptions about IP ratings

Does a higher IP rating always include lower ratings?

For the first digit (solids), yes, IP6X covers everything below. For the second digit (liquids), no. An IP67 device (immersion tested) has not necessarily been tested to IP65 or IP66 (jet tested). The exposures are fundamentally different, submersion applies static pressure, jets apply dynamic pressure. Where both are required, specify a dual rating such as IP66/IP68.

Does IP68 mean a device can be used underwater indefinitely?

No. IP68 requires the manufacturer to define the specific depth and duration. One IP68 device might be rated for 2 m for 30 minutes; another for 5 m continuous. The standard sets the minimum test requirement; the manufacturer specifies the actual conditions. Always check the datasheet, not just the code. indEx iMTB range is IP68 certified up to 580×410×220 for depths of 3 metres deep, for a duration of 2 weeks.

Do IP ratings cover protection against all liquids?

No. IP water tests use fresh water under specific conditions. They say nothing about saltwater, solvents, oils, chemicals, or steam. An IP66 stainless steel enclosure in a chloride-rich marine environment may still suffer corrosion even though water cannot enter, the rating covers ingress, not material compatibility.

Does an IP rating guarantee permanent protection?

No. Gaskets and seals degrade over time, particularly in extreme temperature cycles or with chemical exposure. An IP66 enclosure that has not had its gasket inspected in several years may no longer meet its rating. ATEX enclosures require periodic inspection for exactly this reason.

Common questions

Frequently asked

What does IP65 mean?

IP65 means an enclosure is dust-tight (6) and protected against low-pressure water jets (5): it passes a 3-minute spray from a 6.3 mm nozzle at 12.5 litres per minute from any direction, under IEC 60529. It is not rated for powerful jets or immersion.

What does IP66 mean?

IP66 means dust-tight (6) and protected against powerful water jets (6): a 3-minute spray from a 12.5 mm nozzle at 100 litres per minute from any direction, under IEC 60529. That is eight times the water flow of the IP65 test. indEx enclosures are IP66 as standard.

What does IP67 mean?

IP67 means dust-tight (6) and protected against temporary immersion (7): the enclosure is submerged with its lowest point 1 m below the surface for 30 minutes, under IEC 60529. IP67 does not include the IP66 jet test, so specify IP66/IP67 if you need both.

What is the difference between IP65 and IP66?

Both are dust-tight. The difference is the water jet test: IP65 uses a 6.3 mm nozzle at 12.5 litres per minute (about 30 kPa), IP66 a 12.5 mm nozzle at 100 litres per minute (about 100 kPa). Choose IP66 for exposed outdoor, coastal, offshore or wash-down locations.

Does a higher IP rating always include lower ratings?

For solid particle protection (first digit), yes, IP6X covers everything below. For liquid protection (second digit), no. An IP67 device has been immersion tested but has not necessarily passed the IP65 or IP66 jet tests. The exposures are fundamentally different: submersion applies static pressure; jets apply dynamic pressure. Where both are required, specify a dual rating such as IP66/IP68.

Does IP68 mean a device can be used underwater indefinitely?

No. IP68 requires the manufacturer to define the specific depth and duration. One IP68 device might be rated for 2 m for 30 minutes; another for 5 m continuous. The standard sets the minimum test requirement; the manufacturer specifies the actual conditions. Always check the datasheet, not just the code.

Do IP ratings cover protection against all liquids?

No. IP water tests use fresh water under specific conditions. They say nothing about saltwater, solvents, oils, chemicals, or steam. An IP66 stainless steel enclosure in a chloride-rich marine environment may still suffer corrosion even though water cannot enter, the rating covers ingress, not material compatibility.

Does an IP rating guarantee permanent protection?

No. Gaskets and seals degrade over time, particularly in extreme temperature cycles or with chemical exposure. An IP66 enclosure that has not had its gasket inspected in several years may no longer meet its rating. ATEX enclosures require periodic inspection for exactly this reason.

Get started

Ready to specify?
We'll quote it today.