A systems integrator came to us on behalf of a well-known Scotch whisky producer. The enclosure was for a tank farm, where ethanol vapour makes the area hazardous, and it had to house Siemens ET 200S remote I/O on Weidmüller terminal rails.
The brief
- 1.5mm 316L stainless steel with a brushed finish
- An 1100 x 600 x 300mm iTB-style enclosure
- ATEX certification for Zone 2
- A bottom gland plate for up to 60 x M20 entries. The final approved design used 77 x M16 and 3 x M20 cut-outs on bespoke spacings
- A galvanised mounting plate with the customer's DIN rail and trunking cut-out pattern
What we built
The panel has a left-hand hinged lift-off door with a lockable L-handle, four bolt-on wall lugs, an M10 internal/external earth stud and eight M6 x 25mm rear studs carrying the galvanised mounting plate.
The bottom gland plate was laser cut exactly to the integrator's drawing, with every M16 and M20 entry positioned so that cables land cleanly on the I/O modules above.
How the project ran
We worked with the integrator's design engineer through quote, order, drawing approval and sign-off. The panel went into the tank farm without rework.
Distillery tank farms are typically classified Zone 2 around tanks, pumps and transfer points, where flammable vapour is only expected in abnormal conditions. Our zone classification guide explains how zones are set.