← Case Studies
Case Study April 2026

26 x M20 entries on one ATEX field junction box

Open stainless steel junction box with a dense pattern of cable entry holes in the base

An electrical wholesaler came to us for an end user who was replacing a family of field junction boxes on a hazardous-area process site. The new boxes had to match the existing ones, which had up to 30 x M20 entries in the base, with a terminal bank inside, and be certified Ex e.

The challenge

Our 3D configurator first suggested fewer entries, to stay within the gland spacing rules in the certificate. Once the customer sent the exact tag list and entry pattern of the boxes on site, we re-engineered the layout on 40mm centres. That gave 26 x M20 entries in the base plus 1 x M32 in the top, without stepping outside the certification.

What we built

A 460 x 380 x 150mm iTB in 1.2mm 316L stainless steel with a brushed finish. It has a left-hand hinged lift-off door captivated by a removable locking nut, four bolt-on wall lugs and an engraved white/black/white ID label.

Inside, a galvanised mounting plate on four M6 x 25mm rear studs carries 44 x WDU 2.5mm² beige terminals in one vertical bank, tagged to drawing, plus a horizontal earth bar with 22 x ZB4 terminals. There is an M10 internal/external earth stud on the left-hand side.

Why entry spacing matters

An Ex e certificate sets minimum distances between cable entries so glands can be tightened properly and the enclosure wall stays strong enough. More entries means working closer to those limits, so the layout has to be engineered, not just drilled. The result here was a like-for-like replacement that meets the site's hazardous-area requirements.

What the marking means. Ex eb is increased safety: the enclosure and terminals are built so that no arc, spark or hot surface can occur in normal use, rather than containing an explosion. Ex tb means the enclosure keeps dust out tightly enough for combustible-dust areas, and IP66 confirms it is dust-tight and resists powerful water jets. Category 2 (Gb/Db) equipment is suitable for Zones 1 and 2 (gas) and Zones 21 and 22 (dust). See our Ex eb guide and zone classification guide.

Got a similar requirement? Send us your drawing or spec, or call +44 1233 801 890.