← Resources
ATEX Technical · 7 min read ·20 clicks · 60s avg

What is Ex eb increased safety protection?

Ex eb prevents sparks and excessive surface temperatures from forming in the first place, rather than containing them. It is the most common ATEX protection method for terminal boxes and junction boxes in Zone 1.

What Ex eb means

Ex eb is an ATEX and IECEx protection concept defined in IEC 60079-7. The designation stands for:

  • Ex, explosion protection
  • e, increased safety (Erhöhte Sicherheit in German, the language of the original standard)
  • b, Equipment Protection Level b, suitable for Zone 1

The principle of increased safety is straightforward: design the equipment so that sparks and excessive temperatures simply cannot occur. This is achieved by applying more stringent construction requirements than standard IEC electrical standards, larger creepage distances, better terminal retention, higher ingress protection, and tighter temperature control.

Unlike Ex d (flameproof), Ex eb equipment is not designed to contain an internal explosion. There must be no ignition-capable source inside an Ex eb enclosure. If the equipment inside could spark, for example a contactor or motor winding, then Ex eb alone is not sufficient and combined protection (Ex db/eb) or a different method must be used.

Technical requirements

The key requirements that differentiate Ex eb from standard electrical equipment are defined in IEC 60079-7:

RequirementEx eb specificationReason
Creepage distancesGreater than IEC 60664 for equivalent voltage/pollution degreePrevent tracking between conductors under contamination
Clearance distancesGreater than standard; gas-group dependentPrevent arcing across air gaps
Terminal lockingMust resist accidental loosening; tightening torque specified on certificateLoose connections arc and spark
Ingress protectionMinimum IP54 for Group II equipmentPrevent entry of dust and water that could cause tracking
Maximum voltage11 kV maximum for Group IIHigher voltages require additional precautions
Exposed conductorsNot permitted within the Ex eb enclosureExposed live conductors can arc to adjacent parts
Surface temperatureMust not exceed the T class at maximum loadHot surfaces ignite flammable atmospheres

All of these requirements apply to the equipment as installed, not just as supplied. The installation contractor is responsible for ensuring that torque requirements are met and that cable entries maintain the IP rating.

IP rating requirement

The minimum IP54 requirement for Ex eb Group II equipment is often misunderstood. IP54 means:

  • 5, dust-protected (limited ingress; no harmful deposit)
  • 4, protected against water splashing from any direction

In practice, while most manufacturers offer a lower rating, indEx Enclosures rates all its enclosures to a IP 66 rating, significantly above the minimum. This is partly because the enclosures serve outdoor and industrial environments where higher IP protection is needed regardless, and partly because higher IP ratings provide greater margin against creepage failure over the operating lifetime.

For outdoor installations, IP66 (dust-tight; protection against powerful jets) is standard. The IP rating must be maintained by using appropriately rated cable glands that are correctly installed and torqued.

A certified IP66 enclosure with an incorrectly fitted gland is no longer IP66. The IP rating is only valid as a complete system, enclosure, glands, and blanks all correctly installed.

Terminals and connections

Terminals are the most critical component in an Ex eb enclosure. The certification requires:

  • Terminals must be individually certified to Ex eb (not just suitable by construction)
  • The maximum tightening torque must be marked on the terminal or the enclosure certificate
  • Terminals must include a feature to prevent accidental loosening, a captive screw, locking washer, or spring-loaded clamp
  • The minimum and maximum conductor cross-sections must be specified
  • Creepage between adjacent terminals must meet the standard for the relevant voltage and pollution degree

Polyamide (nylon) terminals are common in Ex eb enclosures because of their good tracking resistance. PE (polyethylene) terminals are used where chemical resistance is required. The terminal material and spacing are verified during type examination, you cannot substitute a different terminal type without re-evaluation.

Wire ferrules (bootlace ferrules) are strongly recommended and often required. Bare stranded conductors in screw terminals can produce loose strands that reduce creepage distances or cause arcing.

Zone suitability

ZoneEx eb suitable?Notes
Zone 0NoZone 0 requires EPL Ga; Ex eb is EPL Gb
Zone 1YesPrimary application; EPL Gb covers Zone 1 and 2
Zone 2YesEx eb is more than sufficient; Ex ec may suffice
Zone 20NoDust Zone 20 requires EPL Da
Zone 21With Ex tbEx tb (dust) combined with Ex eb for dust applications
Zone 22With Ex tcEx tc (dust) combined with Ex ec for Zone 22

For dust hazardous areas, the 't' protection concept applies (IEC 60079-31) rather than 'e'. A terminal box used in a Zone 21 dust area would be marked Ex tb (not Ex eb), even if the construction is similar. The IP requirement for dust zones is typically IP6X (dust-tight).

Typical applications

Ex eb is the standard protection method for a wide range of Zone 1 electrical equipment:

  • Terminal boxes and junction boxes, the most common application; field cable connections in Zone 1 process plant
  • Control station enclosures, pushbutton and pilot light assemblies (using Ex eb certified buttons that cannot spark)
  • Distribution boards, where no switching occurs inside; isolating switches that do switch may require additional protection
  • Marshalling panels, multi-way field cable terminations in Zone 1 substations
  • Instrument junction boxes, where the instruments themselves use intrinsic safety, but the junction box housing the terminals is Ex eb
  • Lighting fittings, fluorescent and LED luminaires certified Ex eb where the lamp and ballast cannot spark
Common questions

Frequently asked

What is Ex eb increased safety?

Ex eb is an ATEX protection concept defined in IEC 60079-7 that prevents sparks and excessive surface temperatures from forming in the first place, by applying additional design measures beyond normal industrial construction: increased creepage and clearance distances, minimum IP54 ingress protection, vibration-resistant certified terminals, and anti-loosening fasteners. It is the most widely used ATEX protection method for terminal boxes and junction boxes in Zone 1 and Zone 2.

What zones does Ex eb cover?

Ex eb covers Zone 1 and Zone 2 for gas and vapour atmospheres. It is classified as EPL Gb (Equipment Protection Level, gas, high protection). For Zone 0, a higher protection level such as Ex ia is required. For dust atmospheres, Ex tb enclosure protection is used instead.

What IP rating is required for Ex eb?

IEC 60079-7 requires a minimum of IP54 for Ex eb enclosures. In practice, while most manufacturers offer a lower rating, indEx Enclosures rates all its enclosures to a IP 66 rating, particularly for UK and offshore applications where weather exposure is common. A higher IP rating than the minimum does not affect the Ex eb classification.

What is the difference between Ex e and Ex eb?

Ex e was the designation under the older CENELEC standard EN 50019. Ex eb is the current designation under IEC 60079-7 (5th edition), which introduced two sub-levels: Ex eb for standard increased safety protection, and Ex ec for Zone 2 only applications. Existing equipment marked Ex e and certified under EN 50019 remains valid and does not need recertifying.

Get started

Ready to specify?
We'll quote it today.